Power-factor relationship

Relationship chart for kW, kVA, kVAr, power factor and power-factor-correction estimates.

  • Type: Relationship chart
  • Scope: Australia
  • Reviewed: 2026-07-13
  • Sensitivity: Low

Power, apparent power and correction relationships

Use these row summaries to read the calculation relationship before checking the value table.

  1. Power factor

    Read PF from real and apparent power values.

    PF = kW / kVA
    Input basis
    One load record with matching kW, kVA, PF and correction target values.
    Output unit
    PF
    Use when
    Use when the load record and PF target describe the same operating condition.
    Boundary
    kW and kVA must belong to the same project load record.
    Not for
    Capacitor-bank selection, switching design or utility approval.
  2. Real power

    Convert apparent power to real power.

    kW = kVA x PF
    Input basis
    One load record with matching kW, kVA, PF and correction target values.
    Output unit
    kW
    Use when
    Use when the load record and PF target describe the same operating condition.
    Boundary
    PF must be entered as a decimal from the project record.
    Not for
    Capacitor-bank selection, switching design or utility approval.
  3. Apparent power

    Estimate kVA from real power.

    kVA = kW / PF
    Input basis
    One load record with matching kW, kVA, PF and correction target values.
    Output unit
    kVA
    Use when
    Use when the load record and PF target describe the same operating condition.
    Boundary
    PF close to zero is not a valid project planning input.
    Not for
    Capacitor-bank selection, switching design or utility approval.
  4. Reactive power

    Show reactive component from kW and kVA.

    kVAr = sqrt(kVA^2 - kW^2)
    Input basis
    One load record with matching kW, kVA, PF and correction target values.
    Output unit
    kVAr
    Use when
    Use when the load record and PF target describe the same operating condition.
    Boundary
    Not equipment selection by itself.
    Not for
    Capacitor-bank selection, switching design or utility approval.
  5. Angle relationship

    Prepare tan(phi) for correction estimates.

    phi = arccos(PF)
    Input basis
    One load record with matching kW, kVA, PF and correction target values.
    Output unit
    rad or deg
    Use when
    Use when the load record and PF target describe the same operating condition.
    Boundary
    Record lagging or leading project context before using a correction relationship.
    Not for
    Capacitor-bank selection, switching design or utility approval.
  6. Correction estimate

    Estimate capacitor kVAr from existing and target PF.

    kVAr = kW x (tan(phi1) - tan(phi2))
    Input basis
    One load record with matching kW, kVA, PF and correction target values.
    Output unit
    kVAr
    Use when
    Use when the load record and PF target describe the same operating condition.
    Boundary
    Manufacturer and utility review still controls selection.
    Not for
    Capacitor-bank selection, switching design or utility approval.
  • Real, apparent and reactive power relationships used by released calculators.
  • Show kW, kVA, kVAr and power-factor relationships without selecting correction equipment.
  • Engineering formula context; utility and equipment requirements govern correction decisions.
  • PF = kW / kVA, phi = arccos(PF), and tan(phi) relationships use values from the same load record.
  • Power-factor correction estimates depend on existing PF, target PF and lagging or leading context; equipment and utility review still controls selection.

Power-factor formulas used for load records

Show kW, kVA, kVAr and power-factor relationships without selecting correction equipment.

Power-factor relationship
RelationshipFormulaUseBoundary
Power factorPF = kW / kVARead PF from real and apparent power values.kW and kVA must belong to the same project load record.
Real powerkW = kVA x PFConvert apparent power to real power.PF must be entered as a decimal from the project record.
Apparent powerkVA = kW / PFEstimate kVA from real power.PF close to zero is not a valid project planning input.
Reactive powerkVAr = sqrt(kVA^2 - kW^2)Show reactive component from kW and kVA.Not equipment selection by itself.
Angle relationshipphi = arccos(PF)Prepare tan(phi) for correction estimates.Record lagging or leading project context before using a correction relationship.
Correction estimatekVAr = kW x (tan(phi1) - tan(phi2))Estimate capacitor kVAr from existing and target PF.Manufacturer and utility review still controls selection.
  • Use calculators for entered values and result warnings.
  • This chart does not choose capacitors or switchgear.

Formula variables

Use these symbols and units when reading the chart rows.

Formula variables
VariableMeaningUnitUse
kWReal power.kW
kVAApparent power.kVA
PFPower factor as a decimal.PF = kW / kVA for the same load record.
phiPower-factor angle.rad or degphi = arccos(PF).
tan(phi)Reactive-power tangent relationship.Used when estimating kVAr correction.
phi1Existing power-factor angle.Derived from the existing PF entered by the user.
phi2Target power-factor angle.Derived from the target PF entered by the user.
kVArReactive power.kVArCorrection estimates still need equipment and utility review.
PF_existingExisting lagging or leading power factor.Leading/lagging context must be recorded before correction planning.
PF_targetTarget power factor.Do not treat the target as a utility approval or product setting.

Worked relationship example

This example shows how one set of entered values reads through the relationship.

kW, kVA and correction relationship reading

An 80 kW load is reviewed from an existing lagging PF of 0.78 toward a target PF of 0.95.

Real power
80 kW
Existing PF
0.78 lagging
Target PF
0.95
  1. Find kVAkVA = kW / PF = 80 / 0.78 = 102.6 kVA.
  2. Use angle relationshipkVAr estimate = kW x (tan phi1 - tan phi2), where phi = arccos(PF).
  3. Estimate correctionUsing the entered PF values gives about 38 kVAr before equipment and utility review.
Correction relationship estimateabout 38 kVAr

This is a relationship example only; capacitor staging, switching and harmonic context need separate review.

Use the result as a power-factor relationship review estimate, not a capacitor selection or network approval.

  • Existing and target PF values describe the same load record.
  • Lagging or leading context is recorded before correction planning.

Where the power-factor chart belongs

Use the chart to understand the formula basis; calculators handle project-specific inputs, warnings and results.

Limits of formula-only correction review
ItemValue
PurposeShow kW, kVA, kVAr and power-factor relationships without selecting correction equipment.
How to use the sourceReal, apparent and reactive power relationships used by released calculators.
Standards and project contextEngineering formula context; utility and equipment requirements govern correction decisions.
Where judgement is still neededUse this chart to understand the relationship behind a calculation; do not treat it as a substitute for entered project values.
Before relying on itConfirm current standards, local authority requirements, DNSP conditions, project documents and manufacturer data before relying on a decision.
Power-factor relationship standards and project context
ContextApplies toPublic boundary
Engineering power relationshipskW, kVA, kVAr, PF, phi and tan(phi) relationshipsThe chart does not select capacitor banks, switchgear, control stages or utility-approved settings.
Utility and equipment reviewExisting PF, target PF and lagging or leading contextUse the result as an estimate before checking tariff, equipment, harmonic and manufacturer requirements.
Project review boundaryPower-factor relationship chartConfirm current Australian standards, local authority requirements, DNSP conditions, project documents and manufacturer data before relying on a decision.

Formula basis for power-factor relationships

Review the cited calculator formulas, utility/equipment boundary and checked date before using these relationships in a correction worksheet.

Power-factor relationship source basis
ItemValue
SourceAUWiring kVA/kW/PF and power-factor-correction calculator formulas.
Source typeReleased calculator formula source
Derivation basisDerived from general electrical power relationships and AUWiring calculator logic.
Last checked2026-07-13
Review intervalAnnual or when calculator formulas or power-factor wording changes.
Review triggerCalculator formula change, equipment-context change or project feedback.
Version usedR10-2026-07-13
Australian applicationAustralia; equipment, utility and project requirements can override general estimates.

Use a calculator for project values

Use the chart to read the formula relationship, then open a calculator when you need entered project values, warnings and result context.

kVA, kW and power factor

Convert between apparent and real power.

Open calculator

Power factor correction

Estimate correction kVAr from entered PF values.

Open calculator