Reactive power kVAr calculator
Calculate Australian reactive power in kVAr from entered kW with power factor or entered kW with kVA values.
Q = sqrt(S^2 - P^2); from kW and PF, S = P / PF; from kW and kVA, PF = P / S- Real power is entered in kW.
- Apparent power is entered in kVA when the kW plus kVA basis is selected.
- Power factor is entered when the kW plus PF basis is selected.
- The calculator flags very low PF for review but does not size correction equipment.
| Variable | Meaning | Unit | Use |
|---|---|---|---|
| P | Real power | kW | Entered real power. |
| S | Apparent power | kVA | Entered or derived apparent power. |
| PF | Power factor | ratio | Entered or derived power factor. |
| Q | Reactive power | kVAr | Reactive side of the power triangle. |
| Angle | Power factor angle | degrees | Arccos of the power factor. |
More
Reactive power kVAr calculator technical guide
Calculate Australian reactive power in kVAr from entered kW with power factor or entered kW with kVA values.
Use this calculator when the immediate question is the reactive-power side of a power triangle. It accepts either kW with power factor, or kW with kVA, and returns kVAr, derived kVA or derived PF, and the PF angle. The output can support Australian power-factor notes, tariff context, plant load records and staged correction discussions.
The calculator is not a correction design tool. It does not size capacitors, choose detuned reactors, check harmonics, assess resonance, evaluate switching controls or confirm manufacturer suitability. It keeps one kVAr relationship visible so the source values can be reviewed.
Reactive Power Use Cases
| Work situation | Entered basis | Useful output | Outside the result |
|---|---|---|---|
| Power-factor worksheet | kW and measured PF | Derived kVA and kVAr | Correction equipment selection |
| Metering summary | kW and kVA | Derived PF and kVAr | Meter accuracy or load profiling |
| Tariff context | Real power and PF from a billing note | Reactive component for discussion | Retailer bill interpretation |
| Capacitor staging handoff | Required or measured reactive component | kVAr value for a staging worksheet | Stage selection or detuning |
| Plant review | Low PF load value | Review note beside kVAr | Harmonic or resonance study |
A useful reactive-power record keeps kW, kVA or PF values tied to the same load condition. A weak record mixes a real-power value from one period with a power factor from another.
Power Triangle Boundary
| Included in this calculator | Not included in this calculator |
|---|---|
| kW plus PF input basis | Capacitor equipment selection |
| kW plus kVA input basis | Harmonic analysis or resonance assessment |
| Derived kVA, PF, kVAr and PF angle | Detuned reactor or switching-control design |
| Invalid relationship check when kVA is below kW | Bill interpretation or tariff recommendation |
| Low-PF review note | Site approval or manufacturer confirmation |
The boundary matters because kVAr is only one side of a broader correction and power-quality question. The result can support a review, but it cannot decide what equipment should be installed.
Input Checklist
| Input | Strong basis | Weak basis |
|---|---|---|
| Reactive reference | Load, meter, switchboard or correction worksheet | Generic note with no project context |
| Input basis | Clear choice between kW plus PF or kW plus kVA | Values copied without knowing what is known |
| Real power | kW value for the same load condition | Estimated kW from another period |
| Apparent power | kVA value paired with the kW value | kVA from a different meter or load |
| Power factor | PF for the same load condition | Assumed PF with no source |
If the values are measured, keep the measurement period and instrument context with the result. If the values are design assumptions, record the source and the operating state being represented.
Review Workflow
- Name the load, meter, correction worksheet or switchboard record.
- Choose whether the known inputs are kW plus PF or kW plus kVA.
- Enter real power in kW.
- Enter PF or kVA from the same operating condition.
- Read kVAr, derived kVA or PF, and PF angle together.
- If PF is very low, check the measurement and load condition before using the record.
- Move to capacitor bank staging only when a staged equipment comparison is the next question.
- Keep harmonics, resonance and manufacturer suitability outside this simple power-triangle record.
The workflow is intentionally transparent. It calculates a relationship; it does not hide correction design decisions inside a formula page.
Worked Australian Examples
| Situation | Inputs | Output reading | Practical note |
|---|---|---|---|
| kW and PF record | 250 kW and PF 0.82 | 304.88 kVA and 174.50 kVAr | Good for a reactive component note. |
| kW and kVA record | 180 kW and 225 kVA | PF 0.80 and 135.00 kVAr | Keep kW and kVA source period together. |
| Low PF review | 160 kW and PF 0.66 | High kVAr with a review note | Check metering and load condition first. |
These examples use standard power-triangle arithmetic and do not decide correction equipment or tariff outcomes.
Related Tools
Use the kVA, kW and power factor calculator when the task is a broader two-value conversion. Use the capacitor bank staging calculator when a required correction value needs to be compared with entered stage sizes. Use the power-factor relationship chart when the user needs the relationship explained rather than calculated.
| Next question | Use next |
|---|---|
| General kVA, kW and PF conversion | kVA, kW and power factor calculator |
| Entered capacitor stages must be compared | Capacitor bank staging calculator |
| Three-phase current is also known | Three-phase power matrix calculator |
| Power triangle needs explanation | Power-factor relationship chart |
Stop Points
- kW and kVA values do not belong to the same operating condition.
- kVA is lower than kW.
- PF is assumed without a source or measurement basis.
- Harmonics, resonance or switching are material to the decision.
- The result is being used to select correction equipment without further review.
Export the result only with the input source, operating condition and intended next use. The kVAr value is a relationship output, not a complete power-quality decision.
kW and PF reactive power record
A power-factor worksheet needs the reactive component from real power and measured PF.
- Reference
- KVAR-1
- Input basis
- kw-pf
- Real power
- 250 kW
- PF or kVA
- 0.82
- Apparent power304.88 kVA
- Power factor0.82
- Reactive power174.5 kVAr
304.88 kVA at PF 0.82.
The result derives the apparent power and kVAr side of the power triangle for the entered operating point.
- Real power is entered in kW.
- Power factor is the measured or documented value for the same operating point.
- Equipment selection is outside this calculator.
kW and kVA triangle record
A metering note has real and apparent power values and needs the reactive component.
- Reference
- KVAR-2
- Input basis
- kw-kva
- Real power
- 180 kW
- PF or kVA
- 225 kVA
- Apparent power225 kVA
- Power factor0.8
- Reactive power135 kVAr
225 kVA at PF 0.8.
The kVAr value follows from the power triangle when real power is less than apparent power.
- kW and kVA are for the same load and period.
- The derived PF is a relationship value.
- Metering uncertainty remains outside the calculation.
Low PF reactive review
A site note checks how large the reactive component becomes at a low entered power factor.
- Reference
- KVAR-3
- Input basis
- kw-pf
- Real power
- 160 kW
- PF or kVA
- 0.66
- Apparent power242.42 kVA
- Power factor0.66
- Reactive power182.12 kVAr
242.42 kVA at PF 0.66.
The page calculates the reactive value but flags the low PF input for metering and load-condition review.
- The PF value is entered from a documented source.
- The calculator does not model harmonics or resonance.
- Correction staging should use a separate worksheet.