Reactive power kVAr calculator

Calculate Australian reactive power in kVAr from entered kW with power factor or entered kW with kVA values.

  • Calculator
  • Power conversion
  • Australia
Use the load, meter or correction worksheet reference.
Choose which values are known.
kW
Enter the real power value.
kVA
Required when the basis is kW + kVA.
PF
Required when the basis is kW + PF.
Q = sqrt(S^2 - P^2); from kW and PF, S = P / PF; from kW and kVA, PF = P / S
  • Real power is entered in kW.
  • Apparent power is entered in kVA when the kW plus kVA basis is selected.
  • Power factor is entered when the kW plus PF basis is selected.
  • The calculator flags very low PF for review but does not size correction equipment.
Formula variables
VariableMeaningUnitUse
PReal powerkWEntered real power.
SApparent powerkVAEntered or derived apparent power.
PFPower factorratioEntered or derived power factor.
QReactive powerkVArReactive side of the power triangle.
AnglePower factor angledegreesArccos of the power factor.
More

Reactive power kVAr calculator technical guide

Calculate Australian reactive power in kVAr from entered kW with power factor or entered kW with kVA values.

Use this calculator when the immediate question is the reactive-power side of a power triangle. It accepts either kW with power factor, or kW with kVA, and returns kVAr, derived kVA or derived PF, and the PF angle. The output can support Australian power-factor notes, tariff context, plant load records and staged correction discussions.

The calculator is not a correction design tool. It does not size capacitors, choose detuned reactors, check harmonics, assess resonance, evaluate switching controls or confirm manufacturer suitability. It keeps one kVAr relationship visible so the source values can be reviewed.

Reactive Power Use Cases

Reactive power use cases
Work situationEntered basisUseful outputOutside the result
Power-factor worksheetkW and measured PFDerived kVA and kVArCorrection equipment selection
Metering summarykW and kVADerived PF and kVArMeter accuracy or load profiling
Tariff contextReal power and PF from a billing noteReactive component for discussionRetailer bill interpretation
Capacitor staging handoffRequired or measured reactive componentkVAr value for a staging worksheetStage selection or detuning
Plant reviewLow PF load valueReview note beside kVArHarmonic or resonance study

A useful reactive-power record keeps kW, kVA or PF values tied to the same load condition. A weak record mixes a real-power value from one period with a power factor from another.

Power Triangle Boundary

Reactive power boundary
Included in this calculatorNot included in this calculator
kW plus PF input basisCapacitor equipment selection
kW plus kVA input basisHarmonic analysis or resonance assessment
Derived kVA, PF, kVAr and PF angleDetuned reactor or switching-control design
Invalid relationship check when kVA is below kWBill interpretation or tariff recommendation
Low-PF review noteSite approval or manufacturer confirmation

The boundary matters because kVAr is only one side of a broader correction and power-quality question. The result can support a review, but it cannot decide what equipment should be installed.

Input Checklist

Values to collect before calculating kVAr
InputStrong basisWeak basis
Reactive referenceLoad, meter, switchboard or correction worksheetGeneric note with no project context
Input basisClear choice between kW plus PF or kW plus kVAValues copied without knowing what is known
Real powerkW value for the same load conditionEstimated kW from another period
Apparent powerkVA value paired with the kW valuekVA from a different meter or load
Power factorPF for the same load conditionAssumed PF with no source

If the values are measured, keep the measurement period and instrument context with the result. If the values are design assumptions, record the source and the operating state being represented.

Review Workflow

  1. Name the load, meter, correction worksheet or switchboard record.
  2. Choose whether the known inputs are kW plus PF or kW plus kVA.
  3. Enter real power in kW.
  4. Enter PF or kVA from the same operating condition.
  5. Read kVAr, derived kVA or PF, and PF angle together.
  6. If PF is very low, check the measurement and load condition before using the record.
  7. Move to capacitor bank staging only when a staged equipment comparison is the next question.
  8. Keep harmonics, resonance and manufacturer suitability outside this simple power-triangle record.

The workflow is intentionally transparent. It calculates a relationship; it does not hide correction design decisions inside a formula page.

Worked Australian Examples

Reactive power examples
SituationInputsOutput readingPractical note
kW and PF record250 kW and PF 0.82304.88 kVA and 174.50 kVArGood for a reactive component note.
kW and kVA record180 kW and 225 kVAPF 0.80 and 135.00 kVArKeep kW and kVA source period together.
Low PF review160 kW and PF 0.66High kVAr with a review noteCheck metering and load condition first.

These examples use standard power-triangle arithmetic and do not decide correction equipment or tariff outcomes.

Related Tools

Use the kVA, kW and power factor calculator when the task is a broader two-value conversion. Use the capacitor bank staging calculator when a required correction value needs to be compared with entered stage sizes. Use the power-factor relationship chart when the user needs the relationship explained rather than calculated.

Next tool selection
Next questionUse next
General kVA, kW and PF conversionkVA, kW and power factor calculator
Entered capacitor stages must be comparedCapacitor bank staging calculator
Three-phase current is also knownThree-phase power matrix calculator
Power triangle needs explanationPower-factor relationship chart

Stop Points

  • kW and kVA values do not belong to the same operating condition.
  • kVA is lower than kW.
  • PF is assumed without a source or measurement basis.
  • Harmonics, resonance or switching are material to the decision.
  • The result is being used to select correction equipment without further review.

Export the result only with the input source, operating condition and intended next use. The kVAr value is a relationship output, not a complete power-quality decision.

kW and PF reactive power record

A power-factor worksheet needs the reactive component from real power and measured PF.

Reference
KVAR-1
Input basis
kw-pf
Real power
250 kW
PF or kVA
0.82
  1. Apparent power304.88 kVA
  2. Power factor0.82
  3. Reactive power174.5 kVAr
Reactive power174.5 kVAr

304.88 kVA at PF 0.82.

The result derives the apparent power and kVAr side of the power triangle for the entered operating point.

  • Real power is entered in kW.
  • Power factor is the measured or documented value for the same operating point.
  • Equipment selection is outside this calculator.

kW and kVA triangle record

A metering note has real and apparent power values and needs the reactive component.

Reference
KVAR-2
Input basis
kw-kva
Real power
180 kW
PF or kVA
225 kVA
  1. Apparent power225 kVA
  2. Power factor0.8
  3. Reactive power135 kVAr
Reactive power135 kVAr

225 kVA at PF 0.8.

The kVAr value follows from the power triangle when real power is less than apparent power.

  • kW and kVA are for the same load and period.
  • The derived PF is a relationship value.
  • Metering uncertainty remains outside the calculation.

Low PF reactive review

A site note checks how large the reactive component becomes at a low entered power factor.

Reference
KVAR-3
Input basis
kw-pf
Real power
160 kW
PF or kVA
0.66
  1. Apparent power242.42 kVA
  2. Power factor0.66
  3. Reactive power182.12 kVAr
Reactive power182.12 kVAr

242.42 kVA at PF 0.66.

The page calculates the reactive value but flags the low PF input for metering and load-condition review.

  • The PF value is entered from a documented source.
  • The calculator does not model harmonics or resonance.
  • Correction staging should use a separate worksheet.

Questions

Can this calculate kVAr from kW and PF?

Yes. Select the kW plus PF basis and enter real power and power factor.

Can this calculate kVAr from kW and kVA?

Yes. Select the kW plus kVA basis and enter real and apparent power values from the same condition.

What if kW is greater than kVA?

The calculator rejects that relationship because apparent power must be at least real power.

Does this size capacitors?

No. It calculates a reactive-power record and does not select capacitor equipment or correction stages.

Why is low PF flagged?

Low PF makes the reactive component large, so the metering value and operating condition should be checked before using the result.