Harmonic THD formulas

Formula chart for total harmonic distortion from fundamental and harmonic RMS magnitudes.

  • Type: Measurement chart
  • Scope: Australia
  • Reviewed: 2026-07-13
  • Sensitivity: Low

THD measurements from one analyser record

Use these row summaries to read the calculation relationship before checking the value table.

  1. Same-record harmonic set

    Keep harmonic RMS inputs from one voltage or current measurement record.

    H2, H3, H5, H7, H11, H13 and H_other come from the same analyser record
    Input basis
    Same-record fundamental and harmonic RMS measurements from one analyser setup.
    Output unit
    measurement record
    Use when
    Use when H1 and harmonic RMS values are from the same voltage or current analyser record.
    Boundary
    Analyser setup, instrument measurement type and time window must be recorded.
    Not for
    Power-quality diagnosis, network compliance claim or equipment suitability decision.
  2. Harmonic RMS sum

    Combine entered harmonic magnitudes.

    Hsum = sqrt(H2^2 + H3^2 + H5^2 + H7^2 + H11^2 + H13^2 + H_other^2)
    Input basis
    Same-record fundamental and harmonic RMS measurements from one analyser setup.
    Output unit
    V or A
    Use when
    Use when H1 and harmonic RMS values are from the same voltage or current analyser record.
    Boundary
    Use consistent RMS units and do not mix voltage and current instrument measurements.
    Not for
    Power-quality diagnosis, network compliance claim or equipment suitability decision.
  3. THD percent

    Display distortion relative to the fundamental.

    THD = Hsum / H1 x 100
    Input basis
    Same-record fundamental and harmonic RMS measurements from one analyser setup.
    Output unit
    %
    Use when
    Use when H1 and harmonic RMS values are from the same voltage or current analyser record.
    Boundary
    H1 must be valid, non-zero and from the same analyser record source.
    Not for
    Power-quality diagnosis, network compliance claim or equipment suitability decision.
  4. Threshold margin

    Compare with an optional user-entered review threshold.

    margin = threshold - THD
    Input basis
    Same-record fundamental and harmonic RMS measurements from one analyser setup.
    Output unit
    %
    Use when
    Use when H1 and harmonic RMS values are from the same voltage or current analyser record.
    Boundary
    AS/NZS 61000, National Electricity Rules, DNSP, equipment or project context may govern the threshold.
    Not for
    Power-quality diagnosis, network compliance claim or equipment suitability decision.
  • THD arithmetic using harmonic RMS magnitudes relative to the fundamental.
  • Show THD formulas without diagnosing equipment or network power-quality conditions by itself.
  • Power-quality measurement context, AS/NZS 61000, National Electricity Rules context, DNSP, equipment, analyser setup and project requirements govern interpretation.
  • Record H1, H2, H3, H5, H7, H11, H13 and H_other as same-record analyser values; AS/NZS 61000 and National Electricity Rules context may matter.

Harmonic RMS rows for THD records

Show THD formulas without diagnosing equipment or network power-quality conditions by itself.

Harmonic THD formulas
RelationshipFormulaUseBoundary
Same-record harmonic setH2, H3, H5, H7, H11, H13 and H_other come from the same analyser recordKeep harmonic RMS inputs from one voltage or current measurement record.Analyser setup, instrument measurement type and time window must be recorded.
Harmonic RMS sumHsum = sqrt(H2^2 + H3^2 + H5^2 + H7^2 + H11^2 + H13^2 + H_other^2)Combine entered harmonic magnitudes.Use consistent RMS units and do not mix voltage and current instrument measurements.
THD percentTHD = Hsum / H1 x 100Display distortion relative to the fundamental.H1 must be valid, non-zero and from the same analyser record source.
Threshold marginmargin = threshold - THDCompare with an optional user-entered review threshold.AS/NZS 61000, National Electricity Rules, DNSP, equipment or project context may govern the threshold.
  • Use the calculator for entered harmonic rows.
  • Power-quality interpretation needs analyser and project context.

Formula variables

Use these symbols and units when reading the chart rows.

Formula variables
VariableMeaningUnitUse
H1Fundamental RMS magnitude.V or A
H2Second harmonic RMS magnitude.V or A
H3Third harmonic RMS magnitude.V or A
H5Fifth harmonic RMS magnitude.V or A
H7Seventh harmonic RMS magnitude.V or A
H11Eleventh harmonic RMS magnitude.V or A
H13Thirteenth harmonic RMS magnitude.V or A
H_otherOther same-record harmonic RMS values.V or A
HsumRMS sum of harmonic magnitudes above the fundamental.V or A
THDTotal harmonic distortion.%Specify voltage THD or current THD.
thresholdOptional entered review threshold.%Threshold margin depends on the selected source, not this chart.
marginOptional difference between threshold and THD.%A review aid, not a universal pass/fail result.

Worked relationship example

This example shows how one set of entered values reads through the relationship.

Voltage THD relationship reading

Fundamental and harmonic RMS magnitudes from the same analyser record are used to read the THD formula.

H1
230 Vfundamental RMS
H5
9 V
H7
6 V
H11 + H13 + other
3 V, 2 V, 4 V
  1. Sum harmonic RMS valuesHsum = sqrt(9^2 + 6^2 + 3^2 + 2^2 + 4^2) = 12.1 V.
  2. Compare with fundamentalTHD% = 12.1 / 230 x 100 = 5.3%.
Voltage THD estimateabout 5.3%

The comparison needs the same-record analyser setup and any selected review threshold.

Use this as formula reading only; power-quality interpretation depends on analyser setup, standards context and project review.

  • Harmonic values are RMS magnitudes from the same analyser record.
  • Voltage THD and current THD are not mixed.

Where the harmonic THD chart belongs

Use the chart to understand the formula basis; calculators handle project-specific inputs, warnings and results.

Limits of formula-only THD review
ItemValue
PurposeShow THD formulas without diagnosing equipment or network power-quality conditions by itself.
How to use the sourceTHD arithmetic using harmonic RMS magnitudes relative to the fundamental.
Standards and project contextPower-quality measurement context, AS/NZS 61000, National Electricity Rules context, DNSP, equipment, analyser setup and project requirements govern interpretation.
Where judgement is still neededUse this chart to understand the relationship behind a calculation; do not treat it as a substitute for entered project values.
Before relying on itConfirm current standards, local authority requirements, DNSP conditions, project documents and manufacturer data before relying on a decision.
Harmonic THD formulas standards and project context
ContextApplies toPublic boundary
Analyser setupH1 and harmonic RMS values from H2, H3, H5, H7, H11, H13 and H_otherUse same-record analyser values and do not mix voltage THD with current THD.
AS/NZS 61000 and National Electricity Rules contextThreshold margin and power-quality interpretationThe chart does not set universal limits or diagnose equipment and network conditions by itself.
Project review boundaryHarmonic THD formulas chartConfirm current Australian standards, local authority requirements, DNSP conditions, project documents and manufacturer data before relying on a decision.

Measurement basis for harmonic THD

Review the cited calculator source, analyser setup, harmonic record basis and Australian power-quality boundary before using these THD formulas.

Harmonic THD formulas source basis
ItemValue
SourceAUWiring harmonic THD calculator formula notes.
Source typeMeasurement record with standards context
Derivation basisDerived from AUWiring calculator logic and user-entered harmonic RMS values.
Last checked2026-07-13
Review intervalAnnual or when THD calculator formulas or measurement wording changes.
Review triggerFormula change, measurement-record change, analyser context change or project feedback.
Version usedR40-2026-07-13
Australian applicationAustralia; instrument setup, DNSP, equipment and project requirements govern formal interpretation.

Use a calculator for project values

Use the chart to read the formula relationship, then open a calculator when you need entered project values, warnings and result context.

Harmonic THD

Calculate THD from entered fundamental and harmonic magnitudes.

Open calculator