Fault-current relationship

Relationship chart for voltage, source impedance, transformer impedance and prospective fault current.

  • Type: Relationship chart
  • Scope: Australia
  • Reviewed: 2026-07-13
  • Sensitivity: Medium

Fault-current relationships before protection review

Use these row summaries to read the calculation relationship before checking the value table.

  1. Ohm-law fault current

    Estimate current from voltage and loop/source impedance.

    I = V / Z
    Input basis
    Recorded voltage, impedance, transformer and device data for the same fault-current review.
    Output unit
    A
    Use when
    Use when the impedance, voltage and device comparison basis are documented.
    Boundary
    Impedance source and voltage basis must be recorded.
    Not for
    Protection coordination study, breaking-capacity approval or device selection.
  2. kA conversion

    Display prospective current in kA.

    Isc_kA = Isc / 1000
    Input basis
    Recorded voltage, impedance, transformer and device data for the same fault-current review.
    Output unit
    kA
    Use when
    Use when the impedance, voltage and device comparison basis are documented.
    Boundary
    Does not set equipment breaking capacity.
    Not for
    Protection coordination study, breaking-capacity approval or device selection.
  3. Transformer full-load current

    Support transformer-based fault estimates.

    FLC = kVA x 1000 / (sqrt(3) x VLL)
    Input basis
    Recorded voltage, impedance, transformer and device data for the same fault-current review.
    Output unit
    A
    Use when
    Use when the impedance, voltage and device comparison basis are documented.
    Boundary
    Voltage source must be line-to-line for three-phase project review.
    Not for
    Protection coordination study, breaking-capacity approval or device selection.
  4. Transformer short-circuit estimate

    Estimate prospective current from transformer impedance.

    Isc = FLC x 100 / Z%
    Input basis
    Recorded voltage, impedance, transformer and device data for the same fault-current review.
    Output unit
    A or kA
    Use when
    Use when the impedance, voltage and device comparison basis are documented.
    Boundary
    Network source and upstream impedance may change the actual value.
    Not for
    Protection coordination study, breaking-capacity approval or device selection.
  5. Breaking-capacity margin

    Record an optional comparison margin before formal review.

    margin = I_breaking - Isc
    Input basis
    Recorded voltage, impedance, transformer and device data for the same fault-current review.
    Output unit
    A or kA
    Use when
    Use when the impedance, voltage and device comparison basis are documented.
    Boundary
    Manufacturer device data, authority requirements and project study control the decision.
    Not for
    Protection coordination study, breaking-capacity approval or device selection.
  • Ohm-law and transformer-impedance relationships used by released calculators.
  • Show the relationships behind fault-current worksheets without replacing protection studies.
  • AS/NZS 3000, AS/NZS 3017 testing context and protection-device data noted for project review.
  • Use AS/NZS 3017 measurement context, manufacturer device data, breaking capacity, loop impedance, source impedance and threshold margin records for formal review.

Impedance and current rows for fault records

Show the relationships behind fault-current worksheets without replacing protection studies.

Fault-current relationship
RelationshipFormulaUseBoundary
Ohm-law fault currentI = V / ZEstimate current from voltage and loop/source impedance.Impedance source and voltage basis must be recorded.
kA conversionIsc_kA = Isc / 1000Display prospective current in kA.Does not set equipment breaking capacity.
Transformer full-load currentFLC = kVA x 1000 / (sqrt(3) x VLL)Support transformer-based fault estimates.Voltage source must be line-to-line for three-phase project review.
Transformer short-circuit estimateIsc = FLC x 100 / Z%Estimate prospective current from transformer impedance.Network source and upstream impedance may change the actual value.
Breaking-capacity marginmargin = I_breaking - IscRecord an optional comparison margin before formal review.Manufacturer device data, authority requirements and project study control the decision.
  • Use the calculators for project-specific values.
  • Protection selection needs device data and competent review.

Formula variables

Use these symbols and units when reading the chart rows.

Formula variables
VariableMeaningUnitUse
VVoltage basis for fault-current estimate.VRecord phase-to-neutral, phase-to-phase or three-phase basis.
VLLLine-to-line voltage used for three-phase transformer current.V
ZLoop impedance or source impedance.ohmRecord whether the value came from measurement, DNSP data or study output.
ZloopMeasured or entered loop impedance.ohmAS/NZS 3017 testing context can affect the record.
ZsourceSource or upstream impedance used by a study.ohmDo not mix with loop measurement without review.
IFault current estimate.A or kA
IscProspective short-circuit current estimate.A or kACompare against breaking capacity only with device data.
Isc_kAProspective short-circuit current expressed in kiloamps.kA
kVATransformer apparent power used for a full-load-current estimate.kVA
sqrt(3)Three-phase line-current factor.Used with a line-to-line voltage basis.
ZpctTransformer impedance percent.%Use transformer data from the current source record.
FLCTransformer full-load current.A
I_breakingProtective-device breaking capacity used for comparison.A or kAUse current manufacturer data and the same current unit as Isc.
marginOptional margin between device breaking capacity and estimated current.kA or %A review aid, not a protection study.

Worked relationship example

This example shows how one set of entered values reads through the relationship.

Loop-impedance fault-current reading

A 230 V phase basis and recorded loop impedance are used to read the Ohm-law relationship.

Voltage basis
230 Vphase-to-neutral example
Recorded impedance
0.35 ohmmeasurement/source record required
  1. Apply Ohm-law relationshipI = V / Z = 230 / 0.35 = 657 A.
  2. Convert for records657 A = 0.66 kA.
  3. Keep review separateBreaking capacity and protection decisions need manufacturer data and competent project review.
Prospective current estimateabout 657 A, or 0.66 kA

The estimate depends on the recorded impedance source and voltage basis.

Use the example as a relationship review record before comparing against device data or protection-study outputs.

  • Impedance source and phase basis are recorded.
  • AS/NZS 3017 testing context and instrument records may affect measured values.

Where the fault-current chart belongs

Use the chart to understand the formula basis; calculators handle project-specific inputs, warnings and results.

Limits of formula-only protection review
ItemValue
PurposeShow the relationships behind fault-current worksheets without replacing protection studies.
How to use the sourceOhm-law and transformer-impedance relationships used by released calculators.
Standards and project contextAS/NZS 3000, AS/NZS 3017 testing context and protection-device data noted for project review.
Where judgement is still neededUse this chart to understand the relationship behind a calculation; do not treat it as a substitute for entered project values.
Before relying on itConfirm current standards, local authority requirements, DNSP conditions, project documents and manufacturer data before relying on a decision.
Fault-current relationship standards and project context
ContextApplies toPublic boundary
AS/NZS 3017 testing contextLoop impedance records and prospective-current estimatesInstrument setup, test method and recorded conditions belong with the measurement record.
Protection-device dataBreaking-capacity comparison, threshold margin and coordination reviewManufacturer data, authority requirements and engineering review govern formal protection decisions.
Source and loop impedanceMeasured loop impedance, DNSP/source data and transformer impedanceDo not mix impedance sources without a documented project basis.

Formula basis for fault-current relationships

Confirm the cited calculator source, impedance basis, device-data boundary and Australian testing context before relying on these fault-current relationships.

Fault-current relationship source basis
ItemValue
SourceAUWiring fault-loop and short-circuit current calculator formulas.
Source typeMeasurement record with standards context
Derivation basisDerived from AUWiring calculator formulas; no protection coordination tables are reproduced.
Last checked2026-07-13
Review intervalAnnual or when protection calculator formulas or standards context changes.
Review triggerCalculator formula change, protection data practice change, standards update or project feedback.
Version usedR17-2026-07-13
Australian applicationAustralia; instrument data, protective-device data, authority and engineering review govern formal studies.

Use a calculator for project values

Use the chart to read the formula relationship, then open a calculator when you need entered project values, warnings and result context.

Fault loop impedance

Estimate fault current from entered loop impedance.

Open calculator

Short-circuit current

Estimate prospective current from source or transformer data.

Open calculator