Cable Capacity Selector from Verified Reference Data
Reverse-calculate the reference ampacity needed for a load and protective device after an entered installation correction factor.
Result
Capacity check
Formula
Calculation logicFormula definitions and substituted values.
Governing current used for the check (A)
max(Design current Ib (A), Protective-device rating In (A))
max(Design current Ib (A), Protective-device rating In (A))Required reference ampacity (A)
Governing current used for the check (A) / Combined installation correction factor
Governing current used for the check (A) / Combined installation correction factorCandidate adjusted capacity (A)
Candidate reference ampacity (A) * Combined installation correction factor
Candidate reference ampacity (A) * Combined installation correction factorCandidate capacity margin (A)
Candidate adjusted capacity (A) - Governing current used for the check (A)
Candidate adjusted capacity (A) - Governing current used for the check (A)Reference ampacity margin (A)
Candidate reference ampacity (A) - Required reference ampacity (A)
Candidate reference ampacity (A) - Required reference ampacity (A)Capacity check
The candidate adjusted capacity is below the governing current. Review the cable reference data and correction factor before selecting it. if Candidate capacity margin (A) < 0; The candidate adjusted capacity meets the governing current. Confirm the exact cable, installation method, voltage drop, fault withstand and applicable requirements separately. otherwise
The candidate adjusted capacity is below the governing current. Review the cable reference data and correction factor before selecting it. if Candidate capacity margin (A) < 0; The candidate adjusted capacity meets the governing current. Confirm the exact cable, installation method, voltage drop, fault withstand and applicable requirements separately. otherwiseBefore relying on the result
- Find the minimum reference ampacity before consulting a cable table
- Compare a candidate cable against Ib, In and a combined correction factor
- Use the required reference ampacity to select a cable from current AS/NZS 3008 or manufacturer data; no licensed table is embedded here.
Related calculators
Cable Derating Factor Calculator
Combine separate ambient, grouping, installation and thermal factors before applying them to a verified reference cable capacity.
Open calculatorCable Size by Earth Fault Loop Impedance
Estimate the maximum route length and fault current from a target fault current and entered line/earth conductor impedances.
Open calculatorCable Size by Voltage-Drop Check
Estimate the minimum conductor area implied by a user-entered reference impedance and voltage-drop limit.
Open calculatorCable Capacity Check
Compare design current and protective-device rating with a user-entered cable ampacity after a verified combined correction factor. No cable tables are included.