Cable Short-Circuit Withstand Calculator
Calculate required conductor area and withstand current from fault current, clearing time and an entered k coefficient.
Result
Short-circuit withstand check
Formula
Calculation logicFormula definitions and substituted values.
Required conductor area (mm²)
Fault current RMS (A) * sqrt(Protective-device clearing time (s)) / Adiabatic k coefficient (A√s/mm²)
Fault current RMS (A) * sqrt(Protective-device clearing time (s)) / Adiabatic k coefficient (A√s/mm²)Estimated withstand current (A)
Adiabatic k coefficient (A√s/mm²) * Selected conductor area (mm²) / sqrt(Protective-device clearing time (s))
Adiabatic k coefficient (A√s/mm²) * Selected conductor area (mm²) / sqrt(Protective-device clearing time (s))Conductor area margin (mm²)
Selected conductor area (mm²) - Required conductor area (mm²)
Selected conductor area (mm²) - Required conductor area (mm²)Withstand-current margin (A)
Estimated withstand current (A) - Fault current RMS (A)
Estimated withstand current (A) - Fault current RMS (A)Short-circuit withstand check
The selected conductor area is below the adiabatic area required by the entered fault current, clearing time and k coefficient. Review the conductor and protective-device data. if Conductor area margin (mm²) < 0; The selected conductor area meets this entered adiabatic comparison. Confirm peak fault duty, terminations, device performance and applicable requirements separately. otherwise
The selected conductor area is below the adiabatic area required by the entered fault current, clearing time and k coefficient. Review the conductor and protective-device data. if Conductor area margin (mm²) < 0; The selected conductor area meets this entered adiabatic comparison. Confirm peak fault duty, terminations, device performance and applicable requirements separately. otherwiseBefore relying on the result
- Check a selected cable against a short-circuit duty
- Compare clearing time sensitivity for a fixed conductor area
- Verify the selected k coefficient, conductor construction, fault type, peak duty, terminations and equipment withstand before final approval.
Related calculators
Circuit Breaker Rating Checks
Compare the entered Ib, In, Iz and prospective-fault/device-interrupt-capacity values as separate arithmetic checks without selecting a device or claiming compliance.
Open calculatorBreaker Selectivity Limit Check
Compare a downstream prospective fault current with a manufacturer-published selectivity limit for one exact protective-device pair.
Open calculatorProtective Conductor Adiabatic Check
Calculate the minimum protective-conductor area, selected-conductor withstand and I²t duty from user-provided fault current, clearing time and k coefficient.
Open calculatorEarth Fault Loop Impedance Estimate
Estimate line-to-earth loop impedance, temperature-adjusted conductor resistance and fault current from user-entered source and conductor data.
Open calculator