Cable Size by Earth Fault Loop Impedance
Estimate the maximum route length and fault current from a target fault current and entered line/earth conductor impedances.
Result
EFLI route check
Formula
Calculation logicFormula definitions and substituted values.
Maximum loop impedance (Ω)
Line-to-earth voltage U0 (V) / Target fault current (A)
Line-to-earth voltage U0 (V) / Target fault current (A)Route Loop Per Km
Line conductor resistance (Ω/km) + Earth conductor resistance (Ω/km)
Line conductor resistance (Ω/km) + Earth conductor resistance (Ω/km)Maximum one-way route length (m)
(Maximum loop impedance (Ω) - External loop impedance (Ω)) * 1000 / Route Loop Per Km
(Maximum loop impedance (Ω) - External loop impedance (Ω)) * 1000 / Route Loop Per KmSelected-route loop impedance (Ω)
External loop impedance (Ω) + Selected one-way route length (m) * Route Loop Per Km / 1000
External loop impedance (Ω) + Selected one-way route length (m) * Route Loop Per Km / 1000Selected-route fault current (A)
Line-to-earth voltage U0 (V) / Selected-route loop impedance (Ω)
Line-to-earth voltage U0 (V) / Selected-route loop impedance (Ω)Route-length margin (m)
Maximum one-way route length (m) - Selected one-way route length (m)
Maximum one-way route length (m) - Selected one-way route length (m)EFLI route check
The selected route is longer than the calculated maximum length for the entered impedance model. Verify the protective-device basis, conductor data and measured loop impedance. if Route-length margin (m) < 0; The selected route is within the calculated maximum length for the entered impedance model. Confirm protective-device disconnection time and verify the installed loop by testing. otherwise
The selected route is longer than the calculated maximum length for the entered impedance model. Verify the protective-device basis, conductor data and measured loop impedance. if Route-length margin (m) < 0; The selected route is within the calculated maximum length for the entered impedance model. Confirm protective-device disconnection time and verify the installed loop by testing. otherwiseBefore relying on the result
- Solve maximum route length for a target fault current
- Compare an entered route with the EFLI limit
- Use the actual protective-device disconnection basis, source impedance, conductor temperature and current Wiring Rules requirements for final design.
Related calculators
Cable Capacity Selector from Verified Reference Data
Reverse-calculate the reference ampacity needed for a load and protective device after an entered installation correction factor.
Open calculatorCable Derating Factor Calculator
Combine separate ambient, grouping, installation and thermal factors before applying them to a verified reference cable capacity.
Open calculatorCable Size by Voltage-Drop Check
Estimate the minimum conductor area implied by a user-entered reference impedance and voltage-drop limit.
Open calculatorCable Capacity Check
Compare design current and protective-device rating with a user-entered cable ampacity after a verified combined correction factor. No cable tables are included.
Open calculator