Voltage Drop and Maximum Length Calculator
Calculate AC voltage drop, the entered voltage-drop limit in volts and the user-limit-based maximum route length from entered conductor impedance data.
Result
Result
Formula
Calculation logicFormula definitions and substituted values.
Sin Phi
sqrt(1 - Power factor ^ 2)
sqrt(1 - Power factor ^ 2)Phase Factor
if Circuit type = three_phase then 1.7320508075689 else 2
if Circuit type = three_phase then 1.7320508075689 else 2PF-weighted impedance component (Ω/km)
Conductor resistance (Ω/km) * Power factor + Conductor reactance (Ω/km) * Sin Phi
Conductor resistance (Ω/km) * Power factor + Conductor reactance (Ω/km) * Sin PhiEstimated voltage drop (V)
Line current (A) * Phase Factor * PF-weighted impedance component (Ω/km) * One-way route length (m) / 1000
Line current (A) * Phase Factor * PF-weighted impedance component (Ω/km) * One-way route length (m) / 1000Estimated voltage drop (%)
Estimated voltage drop (V) / Line voltage (V) * 100
Estimated voltage drop (V) / Line voltage (V) * 100Entered voltage-drop limit (V)
Line voltage (V) * User-selected voltage-drop limit (%) / 100
Line voltage (V) * User-selected voltage-drop limit (%) / 100Maximum one-way length at entered limit (m)
Entered voltage-drop limit (V) * 1000 / (Line current (A) * Phase Factor * PF-weighted impedance component (Ω/km))
Entered voltage-drop limit (V) * 1000 / (Line current (A) * Phase Factor * PF-weighted impedance component (Ω/km))Result
The entered route length is above the maximum length calculated for the entered voltage-drop limit. Review conductor data, route length and the selected design basis. if One-way route length (m) > Maximum one-way length at entered limit (m); The entered route length is within the maximum length calculated for the entered voltage-drop limit. Confirm cable capacity, fault withstand, installation conditions and the applicable Australian requirements separately. otherwise
The entered route length is above the maximum length calculated for the entered voltage-drop limit. Review conductor data, route length and the selected design basis. if One-way route length (m) > Maximum one-way length at entered limit (m); The entered route length is within the maximum length calculated for the entered voltage-drop limit. Confirm cable capacity, fault withstand, installation conditions and the applicable Australian requirements separately. otherwiseBefore relying on the result
- Estimate voltage drop across an entered route
- Solve for maximum length at a user-selected drop percentage
- Compare the arithmetic result with a limit selected from the applicable design basis; no Australian permitted value is assumed.
Related calculators
Cable Capacity Selector from Verified Reference Data
Reverse-calculate the reference ampacity needed for a load and protective device after an entered installation correction factor.
Open calculatorCable Derating Factor Calculator
Combine separate ambient, grouping, installation and thermal factors before applying them to a verified reference cable capacity.
Open calculatorCable Size by Earth Fault Loop Impedance
Estimate the maximum route length and fault current from a target fault current and entered line/earth conductor impedances.
Open calculatorCable Size by Voltage-Drop Check
Estimate the minimum conductor area implied by a user-entered reference impedance and voltage-drop limit.
Open calculator