Estimate pull tension for a horizontal straight run followed by an equivalent cable bend, expose the key intermediate tensions, and compare them with user-entered installation limits.

Inputs

Cable and route

Range: 0.01–100 kg/m

Use the installed cable assembly mass per metre, not the mass of a single core if the route pulls a multicore assembly.

Range: 0–10,000 m

This simplified model treats the straight run as horizontal and uses cable weight as the normal force.

Range: 0–2

Enter a value supported by the cable, conduit/tray, lubricant and pulling method. No universal Australian value is assumed.

Range: 0–100,000 N

Use the measured or planned tension at the start of this modelled segment.

Range: 0–720 degrees

Use the total angle represented by the equivalent bend. A 0° input represents no bend and returns zero sidewall pressure.

Range: 0.001–20 m

Use the effective centreline radius of the bend. Check the cable and pulling-equipment minimum radius separately.

Manufacturer limits

Range: 1–1,000,000 N

Enter the allowable pulling tension for the exact cable construction, grip and pulling method.

Range: 1–10,000,000 N/m

Enter the allowable sidewall pressure for the exact cable and bend/sheave arrangement.

Result

Bend tension multiplication factor
1.369
Estimated exit tension (N)
405.4
Sidewall pressure margin (N/m)
48,648.5
Estimated sidewall pressure (N/m)
1,351.5
Estimated tension after straight run (N)
296.1
Pull tension margin (N)
9,594.6
Limit comparison
Both estimates are within the user-entered limits for this simplified route model.

Formula

Calculation logic

Formula definitions and substituted values.

Before relying on the result

  • Checking a planned pull before installation
  • Comparing a route or lubricant coefficient against manufacturer limits
  • Compare the estimated pull tension and sidewall pressure with the cable and installation equipment manufacturers' stated limits.