RCD and RCBO Trip Test Checker
Compare a measured RCD/RCBO trip current and time with an entered test multiplier and maximum time.
Result
Result
Formula
Calculation logicFormula definitions and substituted values.
Target test current (mA)
RCD rated residual current IΔn (mA) * Test multiplier
RCD rated residual current IΔn (mA) * Test multiplierMeasured current minus target (mA)
Measured trip current (mA) - Target test current (mA)
Measured trip current (mA) - Target test current (mA)Time margin (ms)
Maximum comparison time (ms) - Measured trip time (ms)
Maximum comparison time (ms) - Measured trip time (ms)Entered test passes both comparisons (1=yes)
if Measured trip current (mA) >= Target test current (mA) and Measured trip time (ms) <= Maximum comparison time (ms) then 1 else 0
if Measured trip current (mA) >= Target test current (mA) and Measured trip time (ms) <= Maximum comparison time (ms) then 1 else 0Result
The measured trip current and time meet the entered comparison basis. Confirm the exact device procedure, test instrument and current Australian requirements separately. if Entered test passes both comparisons (1=yes) = 1; The measured trip current or time does not meet the entered comparison basis. Review the device, test multiplier, instrument result and applicable procedure. otherwise
The measured trip current and time meet the entered comparison basis. Confirm the exact device procedure, test instrument and current Australian requirements separately. if Entered test passes both comparisons (1=yes) = 1; The measured trip current or time does not meet the entered comparison basis. Review the device, test multiplier, instrument result and applicable procedure. otherwiseBefore relying on the result
- Check a measured trip test against the selected RCD test basis
- Record current and time margins for a test report
- Use the exact device type, rated residual current, test instrument procedure and current Australian test requirements; this is not a blanket compliance verdict.
Related calculators
Circuit Breaker Rating Checks
Compare the entered Ib, In, Iz and prospective-fault/device-interrupt-capacity values as separate arithmetic checks without selecting a device or claiming compliance.
Open calculatorBreaker Selectivity Limit Check
Compare a downstream prospective fault current with a manufacturer-published selectivity limit for one exact protective-device pair.
Open calculatorCable Short-Circuit Withstand Calculator
Calculate required conductor area and withstand current from fault current, clearing time and an entered k coefficient.
Open calculatorProtective Conductor Adiabatic Check
Calculate the minimum protective-conductor area, selected-conductor withstand and I²t duty from user-provided fault current, clearing time and k coefficient.
Open calculator