PV String Voltage Range Calculator
Apply user-entered module temperature coefficients to estimate cold open-circuit and hot operating string voltage, expose both voltage margins and compare them with entered inverter limits.
Result
Formula
Calculation logicFormula definitions and substituted values.
Estimated module Voc at minimum temperature (V)
Module Voc at STC (V) * (1 + Voc temperature coefficient (%/°C) * (Design minimum module cell temperature (°C) - 25) / 100)
Module Voc at STC (V) * (1 + Voc temperature coefficient (%/°C) * (Design minimum module cell temperature (°C) - 25) / 100)Estimated module Vmp at maximum temperature (V)
Module Vmp at STC (V) * (1 + Vmp temperature coefficient (%/°C) * (Design maximum module cell temperature (°C) - 25) / 100)
Module Vmp at STC (V) * (1 + Vmp temperature coefficient (%/°C) * (Design maximum module cell temperature (°C) - 25) / 100)Estimated cold string Voc (V)
Estimated module Voc at minimum temperature (V) * Modules in proposed series string
Estimated module Voc at minimum temperature (V) * Modules in proposed series stringEstimated hot string Vmp (V)
Estimated module Vmp at maximum temperature (V) * Modules in proposed series string
Estimated module Vmp at maximum temperature (V) * Modules in proposed series stringMaximum modules for entered cold Voc limit
floor(Inverter maximum DC input voltage (V) / Estimated module Voc at minimum temperature (V))
floor(Inverter maximum DC input voltage (V) / Estimated module Voc at minimum temperature (V))Minimum modules for entered hot MPPT limit
ceil(Inverter MPPT minimum voltage (V) / Estimated module Vmp at maximum temperature (V))
ceil(Inverter MPPT minimum voltage (V) / Estimated module Vmp at maximum temperature (V))Cold Voc margin to inverter maximum (V)
Inverter maximum DC input voltage (V) - Estimated cold string Voc (V)
Inverter maximum DC input voltage (V) - Estimated cold string Voc (V)Hot Vmp margin above MPPT minimum (V)
Estimated hot string Vmp (V) - Inverter MPPT minimum voltage (V)
Estimated hot string Vmp (V) - Inverter MPPT minimum voltage (V)Voltage window check
Within the entered voltage bounds if Estimated cold string Voc (V) <= Inverter maximum DC input voltage (V) and Estimated hot string Vmp (V) >= Inverter MPPT minimum voltage (V); Cold string Voc exceeds the entered inverter maximum if Estimated cold string Voc (V) > Inverter maximum DC input voltage (V); Hot string Vmp is below the entered MPPT minimum otherwise
Within the entered voltage bounds if Estimated cold string Voc (V) <= Inverter maximum DC input voltage (V) and Estimated hot string Vmp (V) >= Inverter MPPT minimum voltage (V); Cold string Voc exceeds the entered inverter maximum if Estimated cold string Voc (V) > Inverter maximum DC input voltage (V); Hot string Vmp is below the entered MPPT minimum otherwiseBefore relying on the result
- Check cold-weather string Voc against the inverter maximum
- Check hot-weather string Vmp against the entered MPPT minimum
- Compare the proposed string against the module and inverter voltage data supplied by the user.
Related calculators
EV Charger Cable Sizing Check
Estimate EV charger current, adjusted candidate cable capacity and AC voltage drop for a fixed charging circuit.
Open calculatorEV Charger Supply Capacity Calculator
Estimate signed supply headroom, shortfall and equal per-charger EV charging allocation from a common supply current basis.
Open calculatorMotor Full-Load Current Estimate
Estimate motor electrical input power, apparent input power and full-load line current from rated shaft output, voltage, efficiency, power factor and phase configuration.
Open calculatorMotor Starting Voltage Dip Estimate
Estimate generator-bus voltage dip ratio, voltage change and remaining voltage from motor current and source short-circuit current using a simplified relation.
Open calculator