Neutral Conductor Size with Harmonic Loading
Estimate neutral RMS duty from fundamental imbalance and aligned third-harmonic current, then compare it with corrected neutral capacity.
Result
Result
Formula
Calculation logicFormula definitions and substituted values.
Fundamental neutral component (A)
Fundamental phase current (A) * Fundamental imbalance component (%) / 100
Fundamental phase current (A) * Fundamental imbalance component (%) / 100Third-harmonic neutral component (A)
Fundamental phase current (A) * Third-harmonic component per phase (%) / 100 * 3
Fundamental phase current (A) * Third-harmonic component per phase (%) / 100 * 3Combined modeled neutral RMS (A)
sqrt(Fundamental neutral component (A) * Fundamental neutral component (A) + Third-harmonic neutral component (A) * Third-harmonic neutral component (A))
sqrt(Fundamental neutral component (A) * Fundamental neutral component (A) + Third-harmonic neutral component (A) * Third-harmonic neutral component (A))Corrected neutral capacity (A)
Reference neutral capacity (A) * Neutral correction factor
Reference neutral capacity (A) * Neutral correction factorNeutral capacity margin (A)
Corrected neutral capacity (A) - Combined modeled neutral RMS (A)
Corrected neutral capacity (A) - Combined modeled neutral RMS (A)Result
The corrected neutral capacity is below the modeled neutral RMS duty. Review the harmonic measurements, correction basis and neutral conductor selection. if Neutral capacity margin (A) < 0; The corrected neutral capacity covers the modeled neutral RMS duty for this simplified comparison. Confirm harmonic spectrum, phase arrangement, temperature basis and the applicable Australian requirements separately. otherwise
The corrected neutral capacity is below the modeled neutral RMS duty. Review the harmonic measurements, correction basis and neutral conductor selection. if Neutral capacity margin (A) < 0; The corrected neutral capacity covers the modeled neutral RMS duty for this simplified comparison. Confirm harmonic spectrum, phase arrangement, temperature basis and the applicable Australian requirements separately. otherwiseBefore relying on the result
- Screen a neutral serving office or LED loads with triplen harmonics
- Compare harmonic neutral duty with a derated conductor capacity
- Use measured harmonic data, phase arrangement, transformer connection and the applicable neutral-sizing rules; this is a simplified model of aligned third harmonics.
Related calculators
Circuit Breaker Rating Checks
Compare the entered Ib, In, Iz and prospective-fault/device-interrupt-capacity values as separate arithmetic checks without selecting a device or claiming compliance.
Open calculatorBreaker Selectivity Limit Check
Compare a downstream prospective fault current with a manufacturer-published selectivity limit for one exact protective-device pair.
Open calculatorCable Short-Circuit Withstand Calculator
Calculate required conductor area and withstand current from fault current, clearing time and an entered k coefficient.
Open calculatorProtective Conductor Adiabatic Check
Calculate the minimum protective-conductor area, selected-conductor withstand and I²t duty from user-provided fault current, clearing time and k coefficient.
Open calculator