Skip to content

Single Earth Rod Resistance Estimate

Estimate the resistance of a single vertical rod in uniform soil using the modified Dwight long-rod approximation and user-entered soil resistivity.

Inputs

Soil and rod geometry

Range: 0.1–10,000 Ω·m

Use a site-tested or otherwise traceable soil-resistivity value. The model assumes uniform soil.

Range: 0.5–20 m

Use the effective rod length in contact with the soil. Surface connections and rod-head geometry are outside this model.

Range: 5–100 mm

Use the selected product diameter. Coatings and irregular electrodes are not represented.

Result

Length-to-diameter ratio L/d
125.0
Long-rod logarithmic term
5.908
Estimated rod resistance (Ω)
47.01
Approximation note
This is a uniform-soil single-rod estimate, not a measured or compliance result.

Formula

Calculation logic

Formula definitions and substituted values.

Before relying on the result

  • Comparing rod length and diameter during preliminary layout
  • Estimating resistance from a measured soil resistivity
  • Use the estimate only as a preliminary uniform-soil comparison; verify the site with an appropriate measurement and engineered design.

Related calculators

Use the estimate only as a preliminary uniform-soil comparison; verify the site with an appropriate measurement and engineered design.