Australian Cable Dimensions Reference: Outside Diameter and Product Sizes

Check Australian cable dimensions using manufacturer product references, nominal outside diameters and flat cable sizes for installation planning.

Cable outside diameter must be matched to the manufacturer’s product, not inferred from conductor size alone. A cable marked 2.5 mm² does not have an outside diameter of 2.5 mm: the marking identifies the nominal conductor cross-sectional area. Nexans, for example, lists a nominal overall diameter of 3.6 mm for its 2.5 mm² single-core PVC building wire and 9.8 mm for its 2.5 mm² two-core-and-earth PVC orange circular cable.

Use the product-specific dimensions below as inputs for preliminary containment and routing calculations. Keep the manufacturer’s description of each value: a nominal dimension is not a confirmed maximum dimension or a measurement of the cable being installed.

Cable dimensions by manufacturer and product

These records cover selected Nexans Australia products, not a universal Australian cable diameter chart. All listed conductors are copper. Product references identify the particular catalogue entries checked; the dimensions should not be transferred to another manufacturer or construction simply because the conductor size matches.

Circular cable and insulated building wire

Product and construction Nexans product reference Nominal conductor cross-section Earth conductor cross-section Nominal overall diameter Manufacturer source
Single-core building wire; unsheathed, V-90 PVC insulation; 0.6/1 kV; red BAAP07A5001AARD 1 × 2.5 mm² Not applicable 3.6 mm Nexans building wire product page
PVC orange circular; V-90 insulation and PVC sheath; 450/750 V CNHP07A1002OMAA 2 × 2.5 mm², plus earth 2.5 mm² 9.8 mm Nexans orange circular product page

The building wire dimension includes its insulation, but there is no outer sheath. The orange circular dimension includes the complete sheathed cable. These are different constructions, so their dimensions are not interchangeable.

Flat cable dimensions

Nexans publishes two overall dimensions for the ENVIROLEX low-fire-hazard flat products below. Retain both dimensions rather than treating either as a circular diameter.

All four records are two-core-and-earth cables with copper conductors, X-HF-90 insulation, a grey HFS-90-TP sheath and a 450/750 V rating. The dimensions and product references come from the Nexans ENVIROLEX flat cable range page. /ENVIROLEX%C2%AE36637.html)

Nexans product reference Nominal conductor cross-section Earth conductor cross-section Nominal overall dimensions
CTCP05J5002GXHF 2 × 1.5 mm², plus earth 1.5 mm² 10.0 × 4.6 mm
CTCP07J5002GXHF 2 × 2.5 mm², plus earth 2.5 mm² 12.2 × 5.4 mm
CTCP09J5002GXHF 2 × 4 mm², plus earth 2.5 mm² 13.9 × 6.3 mm
CTCP11J5002GXHF 2 × 6 mm², plus earth 2.5 mm² 15.0 × 6.9 mm

Source for all four records: Nexans Australia. /ENVIROLEX%C2%AE36637.html)

Manufacturer pages checked on 8 November 2026. This is the source-check date, not a manufacturer document revision date. The product references above identify 500 m catalogue entries for the building wire and ENVIROLEX products, and a 100 m entry for the orange circular cable. Packaging length is not an additional cable dimension; confirm the construction and published dimensions before treating another packaging reference as equivalent.

Distinguish conductor size from cable outside diameter

Three different quantities can appear in cable data:

  • Nominal conductor cross-sectional area, in mm², identifies the conductor size.
  • Conductor diameter, in mm, describes the conductor itself where the manufacturer provides that value.
  • Overall cable diameter, in mm, describes the complete circular cable, including insulation and any outer layers.

For containment calculations, OD means the overall outside diameter, not the conductor diameter. The distinction is visible in the orange circular product record: it lists 2.5 mm² conductors, 0.7 mm nominal insulation thickness, 1.2 mm nominal sheath thickness and a 9.8 mm nominal overall diameter. Those values describe different parts of the construction.

Do not attempt to reconstruct a multicore cable’s OD from conductor area and insulation thickness alone. Use the manufacturer’s overall dimension for the assembled product.

The earth conductor size also needs its own field. In the ENVIROLEX records above, the 4 mm² and 6 mm² products both have a 2.5 mm² earth conductor; the main conductor size does not describe every conductor in the cable. /ENVIROLEX%C2%AE36637.html)

Using the dimensions in containment calculations

Circular cable cross-sectional area

For a circular cable, the geometric area occupied by its outside profile is:

[
A_{\text{cable}}=\frac{\pi D^2}{4}
]

where:

  • (A_{\text{cable}}) is the cable’s external cross-sectional area in mm²;
  • (D) is the overall cable diameter in mm.

Using the published nominal OD of 9.8 mm for Nexans CNHP07A1002OMAA:

[
A_{\text{cable}}=\frac{\pi \times 9.8^2}{4}\approx75.4\text{ mm}^2
]

This is a nominal geometric area for the complete cable, not the copper area. For several circular cables, calculate each external area and add the results.

A conduit occupancy calculation also needs the conduit’s internal dimensions and an applicable occupancy method and limit. The sum of cable areas alone does not establish whether the cables can be pulled through the route, particularly where bends, pulling length or tight clearances govern the installation.

Flat cables need a shape-appropriate method

Do not enter the width of a flat cable into a circular-cable formula and treat the result as its actual area. Likewise, multiplying width by thickness gives the area of a bounding rectangle, not necessarily the cable’s actual profile.

For a flat cable, retain both manufacturer dimensions and use a containment method that explicitly addresses that shape. If a calculation accepts only circular OD, its definition must explain how non-circular cables are handled before a flat cable can be represented reliably.

For tray layout, width, thickness, orientation and spacing affect the arrangement. A dimension table supplies the cable geometry; it does not establish current-carrying capacity or the thermal effect of grouping.

Confirm the product before relying on a dimension

Match the cable marking or procurement schedule to the manufacturer, range, product reference, conductor material, core arrangement, conductor sizes, voltage rating, insulation and sheath construction.

Recheck the source when the product changes or clearance is tight. Nexans’ orange circular page specifically notes that a construction change reduced outside diameter and mass for certain smaller conductor sizes. An older catalogue value and a current product-page value may therefore describe different constructions rather than a simple transcription error.

If the available data gives only a nominal dimension, do not silently treat it as a maximum. Obtain a stated dimensional tolerance or maximum from the manufacturer where that distinction affects the decision. For cable already supplied, record any measurement separately from the published nominal value.

Bend radius must also come from the relevant product data and installation condition, not from an assumed universal multiple of OD. For CNHP07A1002OMAA, Nexans lists a minimum bend radius of 59 mm during installation under tension and 39 mm when installed. Those are separate conditions for that product, not general limits for all 2.5 mm² cables.

A verified dimension supports a geometric input. It does not, by itself, confirm cable current-carrying capacity, voltage drop, protection coordination, pulling suitability or acceptance of the complete installation.