Breaker Selectivity Data Finder: Manufacturer Tables and Coordination Guides

Find official breaker selectivity tables and cascading guides, then identify the device details, settings and fault-current limits needed for a check.

Find breaker selectivity data by the exact upstream and downstream protective-device combination—not by rated-current ratio alone. The manufacturer’s table or coordination tool must cover the devices, voltage, trip units and settings being assessed. Schneider Electric’s coordination guide, for example, attaches specific setting conditions to its selectivity tables and warns that lower instantaneous settings can reduce the published selectivity limit.

Use the official sources below to locate that evidence. Selectivity and cascading may appear in the same publication, but they answer different questions: selectivity concerns which protective device operates; cascading concerns the short-circuit protection available from a specified combination.

Official manufacturer data sources

Schneider Electric — Selectivity, Cascading and Coordination Guide

Official entry: Selectivity, Cascading and Coordination Guide, document LVPED318033EN.

The guide covers combinations involving MasterPacT, ComPacT and Acti 9 devices, with separate sections for circuit-breaker selectivity, cascading, selectivity enhanced by cascading, motor circuits and other equipment coordination. For distribution circuit breakers, start in Part A rather than the motor-starter coordination sections.

Useful sections in the PDF retrieved for this reference include:

  • A-1: selectivity terminology and the relationship between device-pair performance and installation fault current.
  • A-7 to A-8: table-use conditions and adjustable trip-unit settings.
  • A-14 onwards: access to circuit-breaker selectivity tables.
  • A-192 onwards: cascading principles and tables.
  • A-215 onwards: selectivity enhanced by cascading.

The download landing page lists version 4.0, released on 3 August 2026, while the PDF retrieved through the download link carries a September 2026 cover date. Retain both the document reference and the date printed in the actual file used for a project; do not identify the evidence solely by the landing-page date.

ABB — SOC, Selected Optimized Coordination

Official entry: ABB SOC coordination tool.

SOC provides separate sections for:

  • Selectivity between short-circuit protective devices.
  • Back-up coordination between short-circuit protective devices.
  • Motor protection.
  • Protection of switch-disconnectors and other devices.

For a breaker-pair selectivity check, choose Selectivity, not Back-up or Motor protection. Record the country, standard and product selections used, together with the resulting table and its conditions. The public SOC entry does not display a fixed publication revision; retain the access date and any version or document identification supplied with the selected result. ABB states that the product ratings and utilisation conditions are defined in the coordination tables.

ABB’s selectivity information page also links its coordination and curve-analysis resources. It distinguishes total selectivity from partial selectivity, which is guaranteed only up to a specified current.

Siemens — Selectivity Tables and SIMARIS resources

Official table: Selectivity Tables for 230/400 and 240/415 V AC, edition 07/2026.

The published title identifies the voltage range and IEC 60947-2 basis. Open the document and check its device coverage, table notes and settings before taking a value from it; the title alone does not establish that a particular pair is included.

For supporting curve work, SIMARIS curves displays protective-device characteristic curves, tolerance bands, settings, cut-off current and let-through energy. It is a curve-analysis resource, not a substitute for a manufacturer-published combination result where one is needed.

Siemens’ SIMARIS planning-tools information also identifies a Selectivity & Back-up Manager for calculating and documenting project-specific selectivity and back-up values. Record the tool and data version with any result used.

These are manufacturer source locations, not confirmation that every product listed internationally is available or applicable in Australia. Match the Australian catalogue device and its documentation to the entry being used.

Decide whether you need selectivity or cascading data

Question Evidence to locate What the result means
Will the downstream device clear the fault without tripping the upstream device? Selectivity or discrimination table for the exact pair A stated selectivity performance, subject to the table’s conditions
Can a specified upstream device provide back-up short-circuit protection for a downstream device? Cascading or back-up table A stated combined short-circuit performance, not proof of selective operation
Can the combination provide both enhanced breaking performance and selectivity? A specific enhanced-selectivity or combined-performance table Separate confirmation of the breaking and selectivity limits

Schneider’s guide treats these as distinct results. Cascading can involve upstream operation, while particular combinations can provide selectivity enhanced by cascading. A cascading entry alone therefore cannot establish selectivity.

Do not estimate cascading performance from current-limitation curves alone. Schneider explicitly directs users to its cascading tables rather than using those curves to infer the reinforced breaking capacity of two breakers.

Identify the pair before reading a table

Keep the upstream device on the supply side and the downstream device on the load side. Reversing them creates a different combination.

For each device, record:

  • Manufacturer, product family and exact catalogue reference.
  • Frame size and breaking-capacity variant.
  • Rated current and trip-unit type or fixed trip curve.
  • Adjustable protection settings relevant to the table.
  • Pole arrangement and any configuration specified by the source.
  • Circuit voltage, AC or DC application, and frequency where specified.

The frame designation alone may be insufficient. Schneider’s guide gives separate instructions for breakers fitted with trip units rated below the frame rating, and its selectivity tables include assumptions for long-time, short-time and instantaneous protection.

Read the introductory notes as well as the row and column headings. A value can be correctly copied yet inapplicable because the actual settings differ from those assumed in the table.

Do not increase an upstream setting simply to reproduce a table’s best selectivity result without checking the protection consequences. The published combination performance does not establish that those settings are suitable for the circuit.

Read numeric limits and “total” entries correctly

A numeric selectivity limit is a fault-current limit, normally expressed in amperes or kiloamperes. It is not the breaker’s rated load current.

Keep the units consistent:

[
1\text{ kA}=1000\text{ A}
]

Also distinguish a numeric limit from a symbol such as “T”. Read the legend in the actual table rather than converting “T” to an unlimited value. Schneider’s guide defines total selectivity up to the downstream breaker’s applicable breaking capacity and distinguishes that from full selectivity up to the installation’s maximum prospective short-circuit current.

The manufacturer’s own example shows why the distinction matters. For a ComPacT NSX100F TMD 100 A upstream of an iC60N curve C 32 A at 400 V AC, the guide gives a 1 kA selectivity limit. It describes the result as partial where the downstream maximum prospective short-circuit current is 5 kA, but full for an installation where that current is 0.8 kA. The device pair has not changed; the installation fault-current condition has.

That example is not a transferable limit for other 100 A and 32 A breakers. The product families, trip units, voltage and applicable table conditions remain part of the result.

Compare the result with the correct installation fault current

Once a numeric limit has been confirmed, compare it with the maximum prospective short-circuit current on the load side of the downstream device, using compatible definitions and units. Schneider’s guide uses this location for its installation-level selectivity assessment.

Let:

  • (I_{\text{psc,max}}) be the maximum downstream prospective short-circuit current in kA.
  • (I_s) be the applicable manufacturer-published selectivity limit in kA.

Where:

[
I_{\text{psc,max}}<I_s
]

the current is below the stated limit. This supports the fault-current comparison only if the pair, settings and other table conditions match. At the boundary, follow the source’s stated inequality and qualification rather than assuming that equality is included.

Where the installation can operate from different sources, retain the source configuration with the fault-current result. Schneider calls for checking different supply cases, such as grid and generator operation, and distinguishes overload, short-circuit and earth-fault selectivity. A single short-circuit limit does not settle every protection function.

AU Wiring’s Breaker Selectivity Limit Check, listed on the calculators home page, compares a downstream prospective fault current with a manufacturer-published selectivity limit for one exact protective-device pair. Finding and validating that limit is a separate task from making the comparison.

If the exact combination is missing

An absent table entry is not permission to use the nearest rated-current combination. It also does not, by itself, prove that the pair has no selectivity.

Request manufacturer confirmation using the full device references, trip units, settings, operating voltage and upstream/downstream arrangement. State whether the required answer concerns a selectivity limit, back-up breaking performance or both.

For mixed-brand devices, obtain evidence that explicitly covers that mixed-brand combination. Two individually valid device data sheets do not establish their joint selectivity performance.

Retain the evidence with the assessment: document reference, revision or cover date, page or table identifier, selected row and column, legend, settings, voltage, result and access date. A result without those conditions cannot reliably be checked later or carried across to a replacement device.