Cable Bend Radius & Installation Data for Australian Wiring

Check product-specific cable bend radius data for pulling and installed conditions, with guidance on dimensions, tension and source verification.

Use the minimum cable bend radius specified for the exact product and the condition being checked. A limit labelled “During Installation (under Tension)” is not interchangeable with an “Installed” limit. Nexans publishes both values for selected Australian low-voltage cables, with a larger minimum radius while the cable is being installed under tension.

A minimum bend radius is a lower limit on the radius of the bend: a larger radius produces a gentler curve. Keep the installation and installed values as separate fields in the same product record so that the condition remains attached to the number.

Product-specific bend radius reference

The following records are for Nexans Australia PVC orange circular cables with stranded copper conductors, V-90 insulation, a PVC outer sheath and a 450/750 V rating. Each earth conductor is 2.5 mm². The product references identify the particular 100 m catalogue entries checked.

Product Nexans product reference Nominal overall diameter Minimum bend radius during installation under tension Minimum bend radius installed
2 × 2.5 mm² plus earth, PVC orange circular CNHP07A1002OMAA 9.8 mm 59 mm 39 mm
4 × 2.5 mm² plus earth, PVC orange circular GNHP07A1004OMAA 12.0 mm 72 mm 48 mm

Sources: Nexans CNHP07A1002OMAA product page and Nexans GNHP07A1004OMAA product page. Manufacturer pages checked on 8 November 2026. This is the source-check date, not a manufacturer document revision date.

These are selected product records, not general limits for every 2.5 mm² cable. The two products have the same nominal conductor cross-section but different core arrangements, overall diameters and published bend radii.

Choose the value for the installation stage

During installation under tension

Use the value explicitly identified for installation under tension when assessing a bend through which the cable will be pulled. Do not substitute the smaller installed value because the cable will eventually remain stationary.

For CNHP07A1002OMAA, the published installation value is 59 mm. A proposed 50 mm cable bend radius is below that value, even though it is above the product’s 39 mm installed minimum.

This distinction matters when planning the pulling route. A cable may need a gentler curve while being pulled than the curve permitted in its final position.

Installed condition

Use the installed value when checking the cable’s final bend geometry against the manufacturer’s installed-condition limit.

For GNHP07A1004OMAA, Nexans lists 48 mm installed and 72 mm during installation under tension. A final bend that meets 48 mm does not establish that pulling the cable through that same geometry meets the installation limit. Both stages need their own comparison.

The installed value also does not establish suitability for repeated flexing or movement. A fixed-position bend limit is not a repeated-flexing specification.

Read radius, diameter and measurement position correctly

Bend radius and bend diameter are different quantities. For the same reference curve:

[
d_{\text{bend}} = 2R
]

where (d_{\text{bend}}) is the bend diameter in millimetres and (R) is the bend radius in millimetres.

The reference curve matters. A radius measured to the inside of the cable is not the same as a radius measured to its centreline or outside surface. Nexans’ high-voltage technical catalogue, for example, expressly states that its recommended bending radii refer to the inside of the curve. That statement belongs to the catalogue’s guidance; it should not be silently treated as a definition for every other product document.

The two low-voltage product pages above label the installation conditions but do not state the radius measurement position in the retrieved product text. Where that distinction affects clearance or acceptance of a proposed bend, obtain the applicable measurement definition from Nexans before comparing it with a drawing or site measurement.

Similarly, a conduit fitting’s catalogue radius or a sheave’s stated diameter cannot be compared directly with a cable bend-radius limit unless the dimensions refer to compatible geometry.

Use diameter multipliers only when the source specifies them

Some manufacturer guidance expresses minimum bend radius as a multiple of cable diameter:

[
R_{\min} = kD
]

where:

  • (R_{\min}) is the minimum bend radius in mm;
  • (k) is the manufacturer’s dimensionless bending factor;
  • (D) is the cable diameter in mm, using the manufacturer’s specified diameter definition.

Nexans uses this relationship in its high-voltage catalogue and identifies a particular diameter definition for nylon-covered cables. The factor and diameter basis must therefore stay together.

Do not derive a universal multiplier from a few product records. For example, the published 59 mm installation radius for the 9.8 mm orange circular cable is approximately six times its nominal diameter, but that arithmetic does not establish a six-diameter rule for other cables. Use the published 59 mm for that product rather than replacing it with a recalculated value.

Where the manufacturer supplies only a factor, retain the factor, diameter definition and installation condition alongside the calculated result. Where it supplies a radius directly, preserve that published value and its units.

Keep pulling tension separate from bend radius

Minimum bend radius and maximum pulling tension describe different constraints. Meeting one does not establish that the other has been met.

The Nexans pages above contain two separately labelled tension fields: “Maximum Pull Tension of Conductor” and “Maximum Pulling Tension”. For CNHP07A1002OMAA, those fields show 0 kN and 1.2 kN respectively; for GNHP07A1004OMAA, they show 1 kN and 1.4 kN. The retrieved pages do not explain how each field relates to the pulling attachment or method.

Those entries should not be collapsed into one tension limit. In particular, the unexplained 0 kN conductor entry is not a usable basis for a pulling calculation. Before adopting a tension value, obtain manufacturer confirmation of:

  • the field that applies to the proposed pulling method;
  • whether the load is applied through the conductors, a pulling stocking or another attachment;
  • the cable components carrying that load;
  • any additional restrictions associated with bends and the installation arrangement.

A bend-radius lookup supplies one mechanical constraint. It does not calculate the tension along a route or establish an allowable sidewall pressure.

Match and retain the installation data

Before using a record, match the supplied cable to the manufacturer, range, product reference, conductor material, conductor sizes, core arrangement, voltage rating, insulation and sheath construction. A conductor-size label alone is insufficient.

Keep the following information together:

Record field Information to retain
Product identity Manufacturer, range and exact product reference
Cable construction Conductor material, main and earth conductor sizes, core arrangement, insulation and sheath
Dimensions Overall diameter or other specified dimensions, including whether values are nominal or maximum
Bend limits Separate installation-under-tension and installed values, with units
Measurement definition Inside, centreline or other manufacturer-defined reference
Pulling limits Exact manufacturer field name, value, units and applicable pulling method
Source Product-page or document link, document revision where available, and date checked

Record missing information as not stated, rather than filling it with a value from a similar cable. If a published record changes, check whether the cable construction has also changed. Nexans notes that a sheath-construction change reduced overall diameter and mass for certain smaller orange circular cables, so an older dimension may describe a different construction.

For a proposed route, compare each bend with the limit for the stage at which the cable passes through or remains in that bend. If a radius is too small, revise the geometry or installation method before relying on the route. A satisfactory radius comparison supports that specific geometric check; it does not confirm pulling suitability, electrical performance or approval of the complete installation.